Church building and health and safety requirements in the UK

By Luke Charalambous · Last reviewed 18 November 2026

Church buildings are used by staff, volunteers, visitors and hirers, so the law treats them much like any other non-domestic premises. The trustees are usually the “responsible person” for fire safety and the duty holder for health and safety. These are the main things to have in place.

Fire safety

Under the Regulatory Reform (Fire Safety) Order 2005, the responsible person must carry out a suitable fire risk assessment and act on it. In England, since 1 October 2023, the whole assessment must be recorded in writing, whatever the size of the church. Review it regularly and whenever the building or how it’s used changes.

Recognised standards also recommend:

  • testing the fire alarm weekly, using a different call point each time, with a professional service at least every 6 months (BS 5839-1)
  • a monthly brief test of emergency lighting and a full-duration test once a year (BS 5266-1)
  • servicing fire extinguishers by a competent person every year (BS 5306-3)
  • a fire drill at least once a year, and a fire log book recording all of this

Electrical and gas safety

The Electricity at Work Regulations 1989 require electrical installations to be kept safe. For a church building there’s no fixed legal interval, but an Electrical Installation Condition Report (EICR) at least every five years is the widely recommended way to show it, and many denominations tie it to the quinquennial inspection. Portable appliance testing (PAT) isn’t a fixed legal requirement either: test equipment based on how much it’s used and how likely it is to be damaged.

Gas appliances must be installed and maintained safely by a Gas Safe registered engineer, and an annual service is recommended. If the church lets out a manse, vicarage or other housing, the landlord rules apply: a gas safety check every 12 months and, in England, an EICR at least every five years.

Water, asbestos and the building fabric

Anyone in control of premises must assess the risk from legionella in the water system and manage it (HSE’s Approved Code of Practice L8). Little-used outlets, showers and stored hot water are the usual risks in churches.

If the building was built or refurbished before 2000, the Control of Asbestos Regulations 2012 give the duty holder a “duty to manage” asbestos: find out whether it’s there (presuming it is unless there’s strong evidence otherwise), record where it is and its condition, and tell anyone who might disturb it, including contractors.

Church of England churches must have a quinquennial inspection by an architect or surveyor at least every five years. Other denominations set their own rules, and a five-yearly survey is good practice for any older building.

Health and safety and first aid

The Health and Safety at Work etc. Act 1974 applies wherever a church employs staff, and churches also owe a duty of care to volunteers and visitors. If you employ five or more people, your health and safety policy and the significant findings of your risk assessments must be written down; for smaller churches it’s still good practice.

Assess what first aid you need (trained first aiders, kits, a defibrillator if you have one registered on The Circuit), keep an accident book, and know which incidents must be reported to HSE under RIDDOR.

Scotland and Northern Ireland

Scotland has its own fire safety law (the Fire (Scotland) Act 2005) and Northern Ireland has the Fire and Rescue Services (NI) Order 2006. Both also require fire risk assessments. The section 156 changes to the fire safety rules apply in England only, so Welsh churches should check Welsh Government guidance.

Key checks and how often

WhatHow oftenWhy
Fire risk assessmentIn writing; reviewed regularly and after any changeRegulatory Reform (Fire Safety) Order 2005
Fire alarmWeekly test; service every 6 monthsBS 5839-1
Emergency lightingMonthly test; full-duration test yearlyBS 5266-1
Fire extinguishersServiced yearlyBS 5306-3
Fire drillAt least once a yearFire Safety Order and HM Government guidance
EICRAt least every 5 years (or as the report says)Electricity at Work Regulations 1989; IET guidance
PAT testingBased on risk and useElectricity at Work Regulations 1989
Gas appliancesServiced yearly by a Gas Safe engineerGas Safety (Installation and Use) Regulations 1998
LegionellaRisk assessment kept up to date; regular checksHSE ACoP L8
AsbestosRegister and management plan; condition rechecked regularlyControl of Asbestos Regulations 2012
Quinquennial inspectionEvery 5 years (Church of England); good practice elsewhereChurch of England rules; good practice for other churches

Common questions

Templates that help

Sources

This is a plain-English summary for churches in the UK, mainly England and Wales. It isn’t legal advice: rules can change and your denomination, insurer or governing document may ask for more, so check the sources and take professional advice where you need it.

Track your buildings and health and safety checks in one place

Comply.Church gives you a checklist for every area, reminds you before anything lapses and fills in the templates with your church’s details. Free to start.

Other guides

All guides and denomination checklists →

comply.church
© 2026 Comply.Church Ltd
AboutPrivacyTermsData Processing AgreementSecurityAccessibilityContact

Comply.Church Ltd is a company registered in England and Wales, company number 17516778.
Registered office: 195–197 Wood Street, Suite RA01, London, E17 3NU.
Registered with the Information Commission (formerly the Information Commissioner’s Office), data protection registration number ZC274213.